The Model 9060 Zirconium Oxide Flue Gas Oxygen Analyzer provides reliable oxygen monitoring by combining proven zirconium oxide sensor technology with a microprocessor based controller. Optimizing combustion efficiency and minimizing exhaust emissions are vital for proper operation of fuel-burning industrial processes. The 9060 provides in-situ analysis capability, accepting signals from up to two zirconium probes in furnaces, kilns, and boilers with sample temperatures ranging from ambient to 1400C. Applications include: Gas, oil, pulverized coal and black liquor boilers; Cement, lime and ceramic kilns; Refinery process heaters and furnaces Blast furnace ovens; Soaking pit and heat treating furnaces; Thermal cracking furnaces; Catalyst regeneration; Asphalt processes; Utility boilers; UOP Process
The low cost 9060L offers fieldconfigurable ranges between 1% and 25% oxygen and has AutoRanging capability and 0-25% oxygen calibration.An optional full scale range is available up to 100%. Two programmable failsafe concentration alarms (one high and one low setpoint) provide the versatility to satisfy nearly any requirement. Membrane command switches and a large, 4-digit LED display make setup and operation clear and quick. - Low cost - Designed for inside installation (but can be modified for outdoor installation) - 4-20 mADC output - Alarm relays - Explosion proof configuration available Probe Lengths Probes can be purchased in varying lengths and explosion proof types are available. Contact Teledyne with your application needs. |
|||||||||
|
Document Control & Training (password) e-mail us: ask_tai@teledyne.com Copyright © 2007 Teledyne Technologies Incorporated. All rights reserved. Teledyne Analytical Instruments 16830 Chestnut St City of Industry, CA 91748 USA |